48V/6kW Power System
Technical Specifications
AC Input | 48V/6kW Power System L+N+PE; 90-300Vac (P-N) |
Frequency | 45-66Hz |
Output Voltage | 42-58Vdc (54 Vdc nominal) |
Output power/current | 6kW/125A |
Low voltage disconnect | Battery LVD (default 100A) |
Battery path protection | 63Ax 1 battery breaker |
Load path protection | 63Ax 1 load breaker |
Remote operation | Ethemet for local/remote monitoring & control via web browser |
Digital Inputs and Outputs | 2 opto isolated digital inputs, 2 NO/NC relay outputs |
Operating temperature | -40 to +75’C |
Applicable rectifiers | Quantum 1.1kW, Serenity 2kW, Serenity 3kW |
Applicable controllers | M1000-H, M1000-X, M2000 |
Applicable standards | EN 60950-1, EN 55022 (Class B), EN 55024, EN 300019-1-1/2/3, ROHS complied |